<?xml version="1.0" encoding="UTF-8"?><xml><records><record><source-app name="Biblio" version="7.x">Drupal-Biblio</source-app><ref-type>17</ref-type><contributors><authors><author><style face="normal" font="default" size="100%">林官明</style></author><author><style face="normal" font="default" size="100%">任阵海</style></author><author><style face="normal" font="default" size="100%">宋建立</style></author></authors></contributors><titles><title><style face="normal" font="default" size="100%">室内颗粒物的稳态置换流净化机制</style></title><secondary-title><style face="normal" font="default" size="100%">中国环境科学</style></secondary-title></titles><dates><year><style  face="normal" font="default" size="100%">2018</style></year></dates><volume><style face="normal" font="default" size="100%">38</style></volume><pages><style face="normal" font="default" size="100%">97-102</style></pages><language><style face="normal" font="default" size="100%">eng</style></language><abstract><style face="normal" font="default" size="100%">对室内颗粒物输运扩散进行了机理上的探讨.用时间空间尺度分析方法,把颗粒物通量分解为宏观平均运动δ尺度的平移滑移,湍流运动的η微尺度的湍流扩散,以及分子运动λ尺度的布朗运动4部分,得到颗粒物通量的系综平均表达式及模式计算表达式,并以此分析总结出提高室内颗粒物净化效率的方法,即低流速及低湍流度梯度.采用数值计算比较了稳态置换流与常规点状上进风上排风形成流场的区别,通过现场实测比较了不同方式安装稳态置换流装置的2个房间的颗粒物数浓度随时间变化,提出并应用剂量加权净化效率对净化效果进行了比较.结果表明,稳态置换流的维持弱正压、线状斜对边进排气口布局、低流速及低湍流度等做法能有效提高净化效率并降低能耗.</style></abstract><issue><style face="normal" font="default" size="100%">1</style></issue></record></records></xml>